These intrinsically safe Modules are compatible with the Rosemount 928 Wireless Gas Monitor. Toxic gas sensors incorporate industry-standard technology that is used in conventional wired gas detectors to bring consistent toxic gas sensing to challenging and remote locations. Combustible gas sensors use Micro‑Electro‑Mechanical Systems (MEMS) technology to classify and detect flammable gas, providing accurate results without use of calibration adjustments.
Rosemount™ 628 Universal Gas Sensor

Spécifications

Température de service
H2S : -40 °C à +50 °C
Appauvrissement en O2 : -30 °C à +50 °C
CO : -30 °C à +50 °C
Précision
H2S ±3 ppm ou 10 % de la lecture, retenir la valeur la plus élevée
Appauvrissement en O2 : ±0,5 % de la lecture
CO : ±6 ppm ou 10 % de la lecture, retenir la valeur la plus élevée
Constante de temps/réponse
T20 < 8 secondes
T50 < 10 secondes
T90 < 45 secondes
Plage de détection
H2S : niveau de concentration de gaz dans une plage de 0-100 ppm
Appauvrissement en O2 : niveau de concentration de gaz de 0-25 % par volume
CO : niveau de concentration de gaz dans une plage de 0-1 000 ppm
Certifications/approbations
Sécurité intrinsèque, CSA div. 1 ANSI/ISA 92.00-2010 (R2015) ; ATEX/IECEx Zone 0

Caractéristiques

  • Compatibility: Rosemount 928 Wireless Gas Monitor (WirelessHART®)
  • Certifications/approvals: Intrinsically Safe, CSA Div 1; ANSI/ISA 92.00-2010 (R2015); ATEX/IECEx Zone 0